In brief
An evacuation lift helps people who cannot use the stairs leave a building during a fire, under a managed plan. A firefighting lift is built for the fire service to reach upper floors safely, with extra protection and controls. In high-rise residential buildings in England, both must be checked every month.
On this page
Plenty of people who manage tall buildings have a lift labelled for firefighters or for evacuation and aren’t quite sure what that means for them. This post explains the two types, how they differ, and the checks the law asks for.
Most lifts are not for use in a fire
The rule most of us learned is simple: in a fire, don’t use the lift. For an ordinary passenger lift, that is still right. Its shaft is not protected to the same degree, its power supply may fail, and it could take someone straight to the floor that is burning.
But some lifts are designed for a fire. They fall into two groups, and they do different jobs.
What an evacuation lift does
An evacuation lift is there for people who can’t use the stairs: wheelchair users, people with mobility problems, and anyone else who would struggle to get down several flights quickly. It is used as part of a managed evacuation plan, usually with trained staff operating it, so that people are moved in a controlled order.
The lift itself has protections an ordinary lift lacks, such as a protected shaft and a secure power supply. But again, it will depend on how your building was designed, so the fire strategy for the building is the document to check.
What a firefighting lift does
A firefighting lift is for the fire service. It lets firefighters and their equipment reach upper floors quickly while the fire is still burning. It sits in a protected firefighting shaft and has controls that let the fire service take over the lift.
The British and European standard for these lifts is BS EN 81-72, which covers firefighters lifts in passenger and goods passenger installations. BS EN 81-73 is a separate standard on how ordinary lifts behave when a fire alarm goes off.
The two side by side
Here is the short version, because the names get mixed up a lot:
| Evacuation lift | Firefighting lift | |
|---|---|---|
| Who uses it in a fire | People who cannot use the stairs, under the building’s evacuation plan | The fire and rescue service |
| Who operates it | Usually trained building staff | Firefighters, using the fire service controls |
| Main purpose | Getting people out | Getting firefighters and equipment up |
| Monthly checks in tall residential blocks in England | Yes | Yes |
A building can have one, both or neither, depending on its height, use and design.
The monthly checks in tall residential blocks
This is where the law has changed in recent years. The Fire Safety (England) Regulations 2022 came into force on 23 January 2023. Regulation 7 applies to the responsible person for a high-rise residential building, meaning one of at least 18 metres or seven storeys. It asks you to:
- Check every lift for firefighters and every evacuation lift at least once a month.
- Report a fault that is not put right within 24 hours to the local fire and rescue authority, electronically.
- Report again once the fault has been fixed.
- Keep a record of the monthly checks and make it available to residents.
These duties sit on top of your existing fire safety duties, not in place of them. They also apply in England only.
What a monthly check involves
The regulations require the check; they don’t hand you a checklist. In a lot of cases, the lift company carries out the monthly check as part of the maintenance contract, and records it in a form you can show residents and the fire service.
If yours doesn’t, ask them to quote for it. The national trade body for the lift industry, LEIA, has published owner guidance on inspecting, maintaining and examining firefighting and evacuation lifts, which is a good starting point for that conversation.
Examination and maintenance still apply
A fire lift is still a lift. It needs regular maintenance like any other, and a thorough examination at least every six months under LOLER, because it carries people. The monthly fire check doesn’t replace either.
A worked example
Say you manage a 12-storey residential block in England with two lifts, one of which is a firefighting lift. Each month, the lift company checks the firefighting lift and its fire service controls and records the result. In March they find a fault with the fire service switch on the ground floor. Parts are ordered but will take three days.
Because the fault won’t be fixed within 24 hours, you report it to the local fire and rescue service. When the part arrives and the lift passes its check, you report that the fault is fixed. The record of both goes into the file residents can see.
If you are not sure which lifts you have
Start with the building’s fire strategy and the lift handover documents. If neither is clear, ask your maintenance company to identify each lift’s type in writing. Not sure your current contract covers the monthly checks? Lift maintenance companies can quote for adding them to the contract.